Image is illustrative
|
Draht H05V-K, 0.75mm² 300/500V -40..70°C, 100m/pck, gnge Code:
H05V-K-0.75-YGR
Price
18,00 €
/pc
Package 100m, unit price
0.18EUR/m
Availability:
In Stock
|
Weight:
0.012 kg/m
|
|
|
|
|
|
Wire H05V-K 0.75mm² 300/500V -40..70°C 100m/pck, yegr
Application range
- For wiring of lamps, devices, switchgear cabinets and distribution boxes
- For installation in tubes, on, in and under plaster as well as in closed installation ducts
- In building with a high density of people or valuable assets
- For use in dry rooms
Design
- Fine-wire strand made of bare copper wires
- Core insulation: Halogen-free
Product features
- The insulation material is halogen-free and free of other materials which could release toxic gases in the event of fire
- Low amount of corrosive gases in the event of fire
- Low smokes/low smoke density in the event of fire according to IEC 61034
- Flame-retardant according to IEC 60332-1-2
|
|
Technical data: |
PVC single cores to DIN VDE 0285-525-2-31 / DIN EN 50525-2-31 and IEC 60227-3 |
Temperature range: |
flexing -5°C to +70°C
fixed installation -30°C to +80°C |
Nominal voltage: |
U0/U 300/500 V |
Test voltage: |
2000 V |
Insulation resistance: |
min. 10 MOhm x km |
Minimum bending radius: |
fixed insatallation 4x core Ø |
Radiation resistance: |
up to 80x106 cJ/kg (up to 80 Mrad) |
Cable structure: |
- Bare Cu-conductor, to DIN VDE 0295 cl.5, fine-wire, BS 6360 cl.5, IEC 60228 cl.5
- Core insulation of PVC compound type TI1 to DIN VDE 0207-363-3 / DIN EN 50363-3 and IEC 60227-3
- Core identification see table below
|
Properties: |
The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers |
Tests: |
PVC self-extinguishing and flame retardant acc. to DIN VDE 0482-332-1-2, DIN EN 60332-1-2, IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B) |
Note: |
The following colours are recommended: black, white, blue, grey, brown, red, orange, turquoise, violet and pink. Exceptions are the colours green and yellow; these are only permitted if the safety regulations allows. Green is permitted for the identification of luminous decorative chains. All 2-coloured combinations of the above single colours are allowed |
Application: |
These single cores are determined for the installation to the inside of apparatus as well as for the protective laying to the lightings, in dry rooms, in production facilities, switch and distributor boards, in tubes, under and surface mounting of plasters. |
|
|