Communication Module IEC 60870-5-104 Server, ProSoft
Communication Module IEC 60870-5-104 Server, ProSoft



Simatic S7-1500, Analog IO Module, 4AI U/I/R/RTD/TC ST, 4-ch. in groups of 4, diagnostics, 2AQ U/I ST, 2-ch. in groups of 2, diagnostics, common-mode 10V, 16bit res., acc. 0.3%, inkl. front con., infeed element, shield bracket, terminal, Siemens
Image is illustrative
Simatic S7-1500, Analog IO Module, 4AI U/I/R/RTD/TC ST, 4-ch. in groups of 4, diagnostics, 2AQ U/I ST, 2-ch. in groups of 2, diagnostics, common-mode 10V, 16bit res., acc. 0.3%, inkl. front con., infeed element, shield bracket, terminal, Siemens
Code: 6ES7534-7QE00-0AB0
Price (indicative)
786,90 €  /pc
Manufacturer :
Availability:
ask for dd
Weight:
0.4389 kg/pc
Volume:
0.0014 m3/pc
 

Simatic S7-1500, Analog IO Module, 4AI U/I/R/RTD/TC ST, 4-ch. in groups of 4, diagnostics, 2AQ U/I ST, 2-ch. in groups of 2, diagnostics, common mode 10V, 16bit res., acc. 0.3%, incl. front con. ^infeed element ^shield bracket ^terminal, Siemens

SIMATIC S7-1500, Analog input/output module AI 4x U/I/R/RTD/TC ST; 4 channels in groups of 4; hardware interrupts; Diagnostics AQ 2x U/I ST; 2 channels in groups of 2; substitute value; Diagnostics COMMON mode voltage approx. 10 V 16 bit; accuracy 0.3% incl. push-in front connector, infeed element, shield bracket, shield terminal
General information
Product type designation AI 4xU/I/RTD/TC /AQ 2xU/I ST
HW functional status FS01
Firmware version V1.0.0
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Measuring range scalable No
● Scalable measured values No
● Adjustment of measuring range No
● Output range scalable No
Engineering with
● STEP 7 TIA Portal configurable/integrated as of version V13 / V13.0.2
● STEP 7 configurable/integrated as of version V5.5 SP3 / -
● PROFIBUS as of GSD version/GSD revision V1.0 / V5.1
● PROFINET as of GSD version/GSD revision V2.3 / -
Operating mode
● Oversampling No
● MSI Yes
● MSO Yes
CiR – Configuration in RUN
Reparameterization possible in RUN Yes
Calibration possible in RUN Yes
Supply voltage
Type of supply voltage DC
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 200 mA; with 24 V DC supply
Encoder supply
24 V encoder supply
● Short-circuit protection Yes
● Output current, max. 20 mA; Max. 47 mA per channel for a duration < 10 s
Power
Power available from the backplane bus 0.7 W
Power loss
Power loss, typ. 3.3 W
Analog inputs
Number of analog inputs 4
● For current measurement 4
● For voltage measurement 4
● For resistance/resistance thermometer measurement 2
● For thermocouple measurement 4
permissible input voltage for voltage input (destruction limit), max. 28.8 V
permissible input current for current input (destruction limit), max. 40 mA
Constant measurement current for resistance-type transmitter, typ. 150 Ohm, 300 Ohm, 600 Ohm, Pt100, Pt200, Ni100: 1.25 mA; 6 000 Ohm, Pt500, Pt1000, Ni1000, LG-Ni1000: 0.625 mA; PTC: 0.472 mA
Technical unit for temperature measurement adjustable Yes; °C/°F/K
Analog input with oversampling No
Standardization of measured values No
Input ranges (rated values), voltages
● 0 to +5 V No
● 0 to +10 V No
● 1 V to 5 V Yes
● Input resistance (1 V to 5 V) 100 kΩ
● -1 V to +1 V Yes
● Input resistance (-1 V to +1 V) 10 MΩ
● -10 V to +10 V Yes
● Input resistance (-10 V to +10 V) 100 kΩ
● -2.5 V to +2.5 V Yes
● Input resistance (-2.5 V to +2.5 V) 10 MΩ
● -25 mV to +25 mV No
● -250 mV to +250 mV Yes
● Input resistance (-250 mV to +250 mV) 10 MΩ
● -5 V to +5 V Yes
● Input resistance (-5 V to +5 V) 100 kΩ
● -50 mV to +50 mV Yes
● Input resistance (-50 mV to +50 mV) 10 MΩ
● -500 mV to +500 mV Yes
● Input resistance (-500 mV to +500 mV) 10 MΩ
● -80 mV to +80 mV Yes
● Input resistance (-80 mV to +80 mV) 10 MΩ
Input ranges (rated values), currents
● 0 to 20 mA Yes
● Input resistance (0 to 20 mA) 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
● -20 mA to +20 mA Yes
● Input resistance (-20 mA to +20 mA) 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
● 4 mA to 20 mA Yes
● Input resistance (4 mA to 20 mA) 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
Input ranges (rated values), thermocouples
● Type B Yes
● Input resistance (Type B) 10 MΩ
● Type C No
● Type E Yes
● Input resistance (Type E) 10 MΩ
● Type J Yes
● Input resistance (type J) 10 MΩ
● Type K Yes
● Input resistance (Type K) 10 MΩ
● Type L No
● Type N Yes
● Input resistance (Type N) 10 MΩ
● Type R Yes
● Input resistance (Type R) 10 MΩ
● Type S Yes
● Input resistance (Type S) 10 MΩ
● Type T Yes
● Input resistance (Type T) 10 MΩ
● Type U No
● Type TXK/TXK(L) to GOST No
Input ranges (rated values), resistance thermometer
● Cu 10 No
● Cu 10 according to GOST No
● Cu 50 No
● Cu 50 according to GOST No
● Cu 100 No
● Cu 100 according to GOST No
● Ni 10 No
● Ni 10 according to GOST No
● Ni 100 Yes; Standard/climate
● Input resistance (Ni 100) 10 MΩ
● Ni 100 according to GOST No
● Ni 1000 Yes; Standard/climate
● Input resistance (Ni 1000) 10 MΩ
● Ni 1000 according to GOST No
● LG-Ni 1000 Yes; Standard/climate
● Input resistance (LG-Ni 1000) 10 MΩ
● Ni 120 No
● Ni 120 according to GOST No
● Ni 200 No
● Ni 200 according to GOST No
● Ni 500 No
● Ni 500 according to GOST No
● Pt 10 No
● Pt 10 according to GOST No
● Pt 50 No
● Pt 50 according to GOST No
● Pt 100 Yes; Standard/climate
● Input resistance (Pt 100) 10 MΩ
● Pt 100 according to GOST No
● Pt 1000 Yes; Standard/climate
● Input resistance (Pt 1000) 10 MΩ
● Pt 1000 according to GOST No
● Pt 200 Yes; Standard/climate
● Input resistance (Pt 200) 10 MΩ
● Pt 200 according to GOST No
● Pt 500 Yes; Standard/climate
● Input resistance (Pt 500) 10 MΩ
● Pt 500 according to GOST No
Input ranges (rated values), resistors
● 0 to 150 ohms Yes
● Input resistance (0 to 150 ohms) 10 MΩ
● 0 to 300 ohms Yes
● Input resistance (0 to 300 ohms) 10 MΩ
● 0 to 600 ohms Yes
● Input resistance (0 to 600 ohms) 10 MΩ
● 0 to 3000 ohms No
● 0 to 6000 ohms Yes
● Input resistance (0 to 6000 ohms) 10 MΩ
● PTC Yes
● Input resistance (PTC) 10 MΩ
Thermocouple (TC)
Temperature compensation
— parameterizable Yes
— internal temperature compensation Yes
— external temperature compensation via RTD Yes
— Compensation for 0 °C reference point temperature Yes; fixed value can be set
— Reference channel of the module No
Cable length
● shielded, max. 800 m; for U/I, 200 m for R/RTD, 50 m for TC
Analog outputs
Number of analog outputs 2
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 24 mA
Current output, no-load voltage, max. 22 V
Cycle time (all channels), min. 3.2 ms; ±0.5 ms, regardless of the number of activated channels
Output ranges, voltage
● 0 to 10 V Yes
● 1 V to 5 V Yes
● -5 V to +5 V No
● -10 V to +10 V Yes
Output ranges, current
● 0 to 20 mA Yes
● -20 mA to +20 mA Yes
● 4 mA to 20 mA Yes
Connection of actuators
● for voltage output two-wire connection Yes
● for voltage output four-wire connection Yes
● for current output two-wire connection Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 1 kΩ; 0.5 kOhm at 1 to 5 V
● with voltage outputs, capacitive load, max. 1 µF
● with current outputs, max. 750 Ω
● with current outputs, inductive load, max. 10 mH
Cable length
● shielded, max. 800 m; for current, 200 m for voltage
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Integration time, parameterizable Yes
● Integration time (ms) 2,5 / 16,67 / 20 / 100 ms
● Basic conversion time, including integration time (ms) 9 / 23 / 27 / 107 ms
— additional conversion time for wire-break monitoring 9 ms
— additional conversion time for resistance measurement 150 ohm, 300 ohm, 600 ohm, Pt100, Pt200, Ni100: 2 ms, 6000 ohm, Pt500, Pt1000, Ni1000, LG-Ni1000, PTC: 4 ms
● Interference voltage suppression for interference frequency f1 in Hz 400 / 60 / 50 / 10
● Time for offset calibration (per module) Basic conversion time of the slowest channel
Smoothing of measured values
● parameterizable Yes
● Step: None Yes
● Step: low Yes
● Step: Medium Yes
● Step: High Yes
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Conversion time (per channel) 0.5 ms
Settling time
● for resistive load 1.5 ms
● for capacitive load 2.5 ms
● for inductive load 2.5 ms
Encoder
Connection of signal encoders
● for voltage measurement Yes
● for current measurement as 2-wire transducer Yes
— Burden of 2-wire transmitter, max. 820 Ω
● for current measurement as 4-wire transducer Yes
● for resistance measurement with two-wire connection Yes; Only for PTC
● for resistance measurement with three-wire connection Yes; All measuring ranges except PTC; internal compensation of the cable resistances
● for resistance measurement with four-wire connection Yes; All measuring ranges except PTC
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.02 %
Temperature error (relative to input range), (+/-) 0.005 %/K; With TC type T 0.02 ± % / K
Crosstalk between the inputs, max. -80 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.02 %
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) 0.02 %
Linearity error (relative to output range), (+/-) 0.15 %
Temperature error (relative to output range), (+/-) 0.002 %/K
Crosstalk between the outputs, max. -100 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) 0.05 %
Temperature error of internal compensation ±6 °C
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 0.3 %
● Current, relative to input range, (+/-) 0.3 %
● Resistance, relative to input range, (+/-) 0.3 %
● Resistance thermometer, relative to input range, (+/-) 0.3 %; Ptxxx standard: ±1.5 K, Ptxxx climate: ±0.5 K, Nixxx standard: ±0.5 K, Nixxx climate: ±0.3 K
● Thermocouple, relative to input range, (+/-) 0.3 %; Type B: > 600 °C ±4.6 K, type E: > -200 °C ±1.5 K, type J: > -210 °C ±1.9 K, type K: > -200 °C ±2.4 K, type N: > -200 °C ±2.9 K, type R: > 0 °C ±4.7 K, type S: > 0 °C ±4.6 K, type T: > -200 °C ±2.4 K
● Voltage, relative to output range, (+/-) 0.3 %
● Current, relative to output range, (+/-) 0.3 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.1 %
● Current, relative to input range, (+/-) 0.1 %
● Resistance, relative to input range, (+/-) 0.1 %
● Resistance thermometer, relative to input range, (+/-) 0.1 %; Ptxxx standard: ±0.7 K, Ptxxx climate: ±0.2 K, Nixxx standard: ±0.3 K, Nixxx climate: ±0.15 K
● Thermocouple, relative to input range, (+/-) 0.1 %; Type B: > 600 °C ±1.7 K, type E: > -200 °C ±0.7 K, type J: > -210 °C ±0.8 K, type K: > -200 °C ±1.2 K, type N: > -200 °C ±1.2 K, type R: > 0 °C ±1.9 K, type S: > 0 °C ±1.9 K, type T: > -200 °C ±0.8 K
● Voltage, relative to output range, (+/-) 0.2 %
● Current, relative to output range, (+/-) 0.2 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 40 dB
● Common mode voltage, max. 10 V
● Common mode interference, min. 60 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal) No
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm Yes
● Limit value alarm Yes; two upper and two lower limit values in each case
Diagnostic messages
● Monitoring the supply voltage Yes
● Wire-break Yes; only for input type 1 ... 5 V, 4 ... 20 mA, TC, R, RTD and output type current
● Short-circuit Yes; Only for output type "voltage"
● Overflow/underflow Yes
Diagnostics indication LED
● RUN LED Yes; Green LED
● ERROR LED Yes; Red LED
● Monitoring of the supply voltage (PWR-LED) Yes; Green LED
● Channel status display Yes; Green LED
● for channel diagnostics Yes; Red LED
● for module diagnostics Yes; Red LED
Potential separation
Potential separation analog inputs
● between the channels No
● between the channels, in groups of 4
● between the channels and backplane bus Yes
● Between the channels and load voltage L+ Yes
Potential separation analog outputs
● between the channels No
● between the channels, in groups of 2
● between the channels and backplane bus Yes
● Between the channels and load voltage L+ Yes
Permissible potential difference
between the inputs (UCM) 20 V DC
Between the inputs and MANA (UCM) 10 V DC
between S- and MANA (UCM) 8 V DC
Isolation
Isolation tested with 707 V DC (type test)
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. 0 °C
● horizontal installation, max. 60 °C
● vertical installation, min. 0 °C
● vertical installation, max. 40 °C
Decentralized operation
Prioritized startup No
Dimensions
Width 25 mm
Height 147 mm
Depth 129 mm
Weights
Weight, approx. 250 g
Other
Note: Supplied incl. 40-pole push-in front connectors. Additional basic error and noise for integration time = 2.5 ms: Voltage: ±250 mV (±0.02%), ±80 mV (±0.05%), ±50 mV (±0.05%); resistance: 150 Ohms (±0.02%); resistance thermometer: Pt100 climate: ±0.08 K, Ni100 climate: ±0.08 K; thermoelement: Type B, R, S: ±3 K, type E, J, K, N, T: ±1 K
last modified: 03/13/2019
 
 