Elit logo e-Elit - leading
electronic and automation component
online distributor
Customer service Mo-Fr 9-17
Call: +49 (0) 511-69608385

Elit shopping basket
Items: Total:
0
0,00 €
    search
Log in
Username/Email Address:

Password:
Show all products categ.
Need assistance?
Featured Products!
Device Marker Grounding, Ø16mm, self-adhesive, -45..80°C, acrylic-coated fibre, 20ea/1pc| 10pc/1pck, Weidmüller, gelb-grün
Device Marker Grounding, Ø16mm, self-adhesive, -45..80°C, acrylic-coated fibre, 20ea/1pc| 10pc/1pck, Weidmüller, gelb-grün



Simatic S7-1500, Analog Output Module, 8AQ8 U/I HS 16bits res., acc. 0.3%, 8-ch. groups of 8, diagnostics, substitute value 8-ch. 0.125ms inkl. infeed element, shield clamp, terminal, Siemens
Image is illustrative
Simatic S7-1500, Analog Output Module, 8AQ8 U/I HS 16bits res., acc. 0.3%, 8-ch. groups of 8, diagnostics, substitute value 8-ch. 0.125ms inkl. infeed element, shield clamp, terminal, Siemens
Code: 6ES7532-5HF00-0AB0
Price (indicative)
963,80 €  /pc
Manufacturer :
Availability:
21 days
Weight:
0.4568 kg/pc
Volume:
0.0013 m3/pc
 

Simatic S7-1500, Analog Output Module AQ8x U/I HS 16bits res., acc. 0.3%, 8-ch. groups of 8, diagnostics, substitute value 8-ch. 0.125ms incl. infeed element, shield clamp ?terminal, Siemens

General information
Product type designation AQ 8xU/I HS
HW functional status FS01
Firmware version V2.1.0
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Output range scalable No
Engineering with
● STEP 7 TIA Portal configurable/integrated as of version V14 / -
● STEP 7 configurable/integrated as of version V5.5 SP3 / -
● PROFIBUS as of GSD version/GSD revision V1.0 / V5.1
● PROFINET as of GSD version/GSD revision V2.3 / -
Operating mode
● Oversampling Yes
● MSO Yes
CiR – Configuration in RUN
Reparameterization possible in RUN Yes
Calibration possible in RUN Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 260 mA; with 24 V DC supply
Power
Power available from the backplane bus 1.15 W
Power loss
Power loss, typ. 7 W
Analog outputs
Number of analog outputs 8
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 45 mA
Current output, no-load voltage, max. 20 V
Cycle time (all channels), min. 125 µs; independent of number of activated channels
Output ranges, voltage
● 0 to 10 V Yes
● 1 V to 5 V Yes
● -5 V to +5 V No
● -10 V to +10 V Yes
Output ranges, current
● 0 to 20 mA Yes
● -20 mA to +20 mA Yes
● 4 mA to 20 mA Yes
Connection of actuators
● for voltage output two-wire connection Yes
● for voltage output four-wire connection Yes
● for current output two-wire connection Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 1 kΩ
● with voltage outputs, capacitive load, max. 100 nF
● with current outputs, max. 500 Ω
● with current outputs, inductive load, max. 1 mH
Cable length
● shielded, max. 200 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Conversion time (per channel) 50 µs; independent of number of activated channels
Settling time
● for resistive load 30 µs; see additional description in the manual
● for capacitive load 100 µs; see additional description in the manual
● for inductive load 100 µs; see additional description in the manual
Errors/accuracies
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) 0.02 %
Linearity error (relative to output range), (+/-) 0.15 %
Temperature error (relative to output range), (+/-) 0.002 %/K
Crosstalk between the outputs, max. -100 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) 0.05 %
Operational error limit in overall temperature range
● Voltage, relative to output range, (+/-) 0.3 %
● Current, relative to output range, (+/-) 0.3 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to output range, (+/-) 0.2 %
● Current, relative to output range, (+/-) 0.2 %
Isochronous mode
Isochronous operation (application synchronized up to terminal) Yes
Execution and activation time (TCO), min. 100 µs
Bus cycle time (TDP), min. 250 µs
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm Yes
Diagnostic messages
● Monitoring the supply voltage Yes
● Wire-break Yes; Only for output type "current"
● Short-circuit Yes; Only for output type "voltage"
● Overflow/underflow Yes
Diagnostics indication LED
● RUN LED Yes; Green LED
● ERROR LED Yes; Red LED
● Monitoring of the supply voltage (PWR-LED) Yes; Green LED
● Channel status display Yes; Green LED
● for channel diagnostics Yes; Red LED
● for module diagnostics Yes; Red LED
Potential separation
Potential separation channels
● between the channels No
● between the channels, in groups of 8
● between the channels and backplane bus Yes
● Between the channels and load voltage L+ Yes
Permissible potential difference
between S- and MANA (UCM) 8 V DC
Isolation
Isolation tested with 707 V DC (type test)
Decentralized operation
Prioritized startup No
Dimensions
Width 35 mm
Height 147 mm
Depth 129 mm
Weights
Weight 325 g
last modified: 11/21/2017
 
 