Elit logo e-Elit - leading
electronic and automation component
online distributor
Customer service Mo-Fr 9-17
Call: +49 (0) 511-69608385

Elit shopping basket
Items: Total:
0
0,00 €
    search
Log in
Username/Email Address:

Password:
Show all products categ.
Need assistance?
Featured Products!
Cantilever Shelf 19in, 2U D300, load 25kg, incl. bolt kit, black
Cantilever Shelf 19in, 2U D300, load 25kg, incl. bolt kit, black



Simatic S7-300, Analog Output SM 332, isolated by channel, 4AI, res. 16bit, 0..10V, 1..5V, ±10V, ±20mA, 0/4..20mA, 20pole, suitable for isochronous mode, improved bus cycle times for the isochronous mode
Image is illustrative
Simatic S7-300, Analog Output SM 332, isolated by channel, 4AI, res. 16bit, 0..10V, 1..5V, ±10V, ±20mA, 0/4..20mA, 20pole, suitable for isochronous mode, improved bus cycle times for the isochronous mode
Code: 6ES7332-7ND02-0AB0
Price (indicative)
772,30 €  /pc
Manufacturer :
Availability:
14 days
Weight:
0.3098 kg/pc
Volume:
0.001 m3/pc
 

Simatic S7-300, Analog Output SM 332, isolated by channel, 4AI, res. 16bit, 0..10V ˄1..5V ˄±10V ˄±20mA ˄0/4..20mA, 20pole, suitable for isochronous mode, improved bus cycle times for the isochronous mode, Siemens

SIMATIC S7-300, Analog output SM 332, isolated by channel, 4 AI, Resolution 16 bit, 0-10 V, 1-5 V, +/-10 V, +/-20 mA, 0/4-20mA, 20-pole, suitable for isochronous mode improved bus cycle times for the isochronous mode
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 290 mA
from backplane bus 5 V DC, max. 120 mA
Power loss
Power loss, typ. 3 W
Analog outputs
Number of analog outputs 4; Isochronous mode
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 40 mA
Current output, no-load voltage, max. 18 V
Output ranges, voltage
● 0 to 10 V Yes
● 1 V to 5 V Yes
● -10 V to +10 V Yes
Output ranges, current
● 0 to 20 mA Yes
● -20 mA to +20 mA Yes
● 4 mA to 20 mA Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 1 kΩ
● with voltage outputs, capacitive load, max. 1 µF
● with current outputs, max. 500 Ω
● with current outputs, inductive load, max. 1 mH
Cable length
● shielded, max. 200 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Conversion time (per channel) 200 µs; in isochronous mode 640 µs
Settling time
● for resistive load 0.2 ms
● for capacitive load 3.3 ms
● for inductive load 0.5 ms
Errors/accuracies
Operational error limit in overall temperature range
● Voltage, relative to output range, (+/-) 0.12 %
● Current, relative to output range, (+/-) 0.18 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to output range, (+/-) 0.02 %
● Current, relative to output range, (+/-) 0.02 %
Interrupts/diagnostics/status information
Diagnostics function Yes; Parameterizable
Substitute values connectable Yes; Parameterizable
Alarms
● Diagnostic alarm Yes; Parameterizable
Diagnostic messages
● Diagnostic information readable Yes
Diagnostics indication LED
● Group error SF (red) Yes
Potential separation
Potential separation analog outputs
● between the channels and backplane bus Yes
Isolation
Isolation tested with 1500 V DC
Connection method
required front connector 20-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 117 mm
Weights
Weight, approx. 220 g