Elit logo e-Elit - leading
electronic and automation component
online distributor
Customer service Mo-Fr 9-17
Call: +49 (0) 511-69608385

Elit shopping basket
Items: Total:
0
0,00 €
    search
Log in
Username/Email Address:

Password:
Show all products categ.
Need assistance?
Featured Products!
Heat Shrink Tubing H-2(Z), 9.5/4.8mm, thin-wall 0.56mm, crosslinked polyolefin -55..125°C/ +100°C, flame resistant, high flexibility, L1.22m/pc, schwarz
Heat Shrink Tubing H-2(Z), 9.5/4.8mm, thin-wall 0.56mm, crosslinked polyolefin -55..125°C/ +100°C, flame resistant, high flexibility, L1.22m/pc, schwarz



Simatic DP, HART Analog Input SM331, 8AI, 0/4..20mA HART, ET200M M153-2, 20poles, FW update, HART secondary variables, rotundancy, local diagnostic buffer timestamp, Siemens
Image is illustrative
Simatic DP, HART Analog Input SM331, 8AI, 0/4..20mA HART, ET200M M153-2, 20poles, FW update, HART secondary variables, rotundancy, local diagnostic buffer timestamp, Siemens
Code: 6ES7331-7TF01-0AB0
Price (indicative)
1.116,40 €  /pc
Manufacturer :
Availability:
21 days
Weight:
0.2636 kg/pc
Volume:
0.001 m3/pc
 

Simatic DP, HART Analog Input SM331, 8AI, 0/4..20mA HART, ET200M M153-2, 20poles, FW update, HART secondary variables, redundancy, local diagnostic buffer timestamp, Siemens

SIMATIC DP, HART analog input SM 331, 8 AI, 0/4 - 20 mA HART, for ET200M with IM153-2, 1 x 20-pole, Functions: FW update, HART auxiliary variables, redundancy, local diagnostic buffer with time stamping,
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 20 mA
from backplane bus 5 V DC, max. 120 mA
Output voltage
Power supply to the transmitters
● present Yes
● Rated value (DC) 24 V
● short-circuit proof Yes
● Supply current, max. 60 mA
Power loss
Power loss, typ. 1.5 W
Analog inputs
Number of analog inputs 8
permissible input current for current input (destruction limit), max. 40 mA
Input ranges (rated values), currents
● 0 to 20 mA Yes
● Input resistance (0 to 20 mA) 140 Ω
● Input resistance (-20 mA to +20 mA) 140 Ω
● Input resistance (4 mA to 20 mA) 140 Ω
Cable length
● shielded, max. 800 m
Analog value generation for the inputs
Measurement principle Sigma Delta
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Integration time, parameterizable Yes
● Integration time (ms) 20 ms at 50 Hz; 16.6 ms at 60 Hz; 100 ms at 100 Hz
● Basic conversion time, including integration time (ms) 55 ms @ 60 Hz, 65 ms @ 50 Hz, 305 ms @ 100 Hz
● Interference voltage suppression for interference frequency f1 in Hz 10 / 50 / 60 Hz
Smoothing of measured values
● parameterizable Yes
● Step: None Yes
● Step: low Yes
● Step: Medium Yes
● Step: High Yes
Encoder
Connection of signal encoders
● for current measurement as 2-wire transducer Yes
● for current measurement as 4-wire transducer Yes
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %
Temperature error (relative to input range), (+/-) 0.001 %/K
Crosstalk between the inputs, min. 70 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.1 %
Operational error limit in overall temperature range
● Current, relative to input range, (+/-) 0.15 %
Basic error limit (operational limit at 25 °C)
● Current, relative to input range, (+/-) 0.1 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 40 dB
● Common mode interference, min. 100 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal) No
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
● Limit value alarm Yes
Diagnostic messages
● Diagnostic information readable Yes
Diagnostics indication LED
● Group error SF (red) Yes
● Channel fault indicator F (red) Yes
Potential separation
Potential separation analog inputs
● between the channels No
● between the channels and backplane bus Yes
Isolation
Isolation tested with 500 V DC
Degree and class of protection
IP degree of protection IP20
Connection method
required front connector 20-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 117 mm
Weights
Weight, approx. 205 g
last modified: 06/06/2019
 
 
AIS.Hensch | e-mail: info@ais-deutschland.de | +49 (0) 511-69608385 | 2021 ©


 
X
 