Featured Products!
AC Output Module SLC500, 16-ch., 120/240VAC, Allen-Bradley
AC Output Module SLC500, 16-ch., 120/240VAC, Allen-Bradley



Simatic S7-300, CPU 315F-2DP Fail-Safe Module, MPI integrated PS 24VDC, working memory 384kB, W40mm, 2. interface DP master/slave, micro memory card required, Siemens
Image is illustrative
Simatic S7-300, CPU 315F-2DP Fail-Safe Module, MPI integrated PS 24VDC, working memory 384kB, W40mm, 2. interface DP master/slave, micro memory card required, Siemens
Code: 6ES7315-6FF04-0AB0
Price (indicative)
1.980,70 €  /pc
Manufacturer :
Availability:
21 days
Weight:
0.339 kg/pc
Volume:
0.001 m3/pc
 

Simatic S7-300, CPU 315F-2DP FailSafe CPU w. MPI Interface, integrated 24VDC power supply, 384kB working memory, W40mm, 2. interface DP-master/slave, micro memory card required, Siemens

General information
HW functional status 01
Firmware version V3.3
Engineering with
● Programming package STEP 7 V5.5 + SP1 or higher or STEP 7 V5.2 + SP1 or higher with HSP 218 + Distributed Safety
Supply voltage
Rated value (DC)
● 24 V DC Yes
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
external protection for power supply lines (recommendation) 2 A min.
Mains buffering
● Mains/voltage failure stored energy time 5 ms
● Repeat rate, min. 1 s
Input current
Current consumption (rated value) 850 mA
Current consumption (in no-load operation), typ. 150 mA
Inrush current, typ. 3.5 A
I²t 1 A²·s
Power loss
Power loss, typ. 4.5 W
Memory
Work memory
● integrated 384 kbyte
● expandable No
● Size of retentive memory for retentive data blocks 128 kbyte
Load memory
● Plug-in (MMC) Yes
● Plug-in (MMC), max. 8 Mbyte
● Data management on MMC (after last programming), min. 10 y
Backup
● present Yes; Guaranteed by MMC (maintenance-free)
● without battery Yes; Program and data
CPU processing times
for bit operations, typ. 0.05 µs
for word operations, typ. 0.09 µs
for fixed point arithmetic, typ. 0.12 µs
for floating point arithmetic, typ. 0.45 µs
CPU-blocks
Number of blocks (total) 1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.
DB
● Number, max. 1 024; Number range: 1 to 16000
● Size, max. 64 kbyte
FB
● Number, max. 1 024; Number range: 0 to 7999
● Size, max. 64 kbyte
FC
● Number, max. 1 024; Number range: 0 to 7999
● Size, max. 64 kbyte
OB
● Description see instruction list
● Size, max. 64 kbyte
● Number of free cycle OBs 1; OB 1
● Number of time alarm OBs 1; OB 10
● Number of delay alarm OBs 2; OB 20, 21
● Number of cyclic interrupt OBs 4; OB 32, 33, 34, 35
● Number of process alarm OBs 1; OB 40
● Number of DPV1 alarm OBs 3; OB 55, 56, 57
● Number of isochronous mode OBs 1; OB 61
● Number of startup OBs 1; OB 100
● Number of asynchronous error OBs 5; OB 80, 82, 85, 86, 87
● Number of synchronous error OBs 2; OB 121, 122
Nesting depth
● per priority class 16
● additional within an error OB 4
Counters, timers and their retentivity
S7 counter
● Number 256
Retentivity
— adjustable Yes
— lower limit 0
— upper limit 255
— preset Z 0 to Z 7
Counting range
— lower limit 0
— upper limit 999
IEC counter
● Number Unlimited (limited only by RAM capacity)
S7 times
● Number 256
Retentivity
— adjustable Yes
— lower limit 0
— upper limit 255
— preset No retentivity
Time range
— lower limit 10 ms
— upper limit 9 990 s
IEC timer
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area in total All, 128 KB max.
Flag
● Number, max. 2 048 byte
● Retentivity available Yes; MB 0 to MB 2047
● Retentivity preset MB 0 to MB 15
● Number of clock memories 8; 1 memory byte
Data blocks
● Retentivity adjustable Yes; via non-retain property on DB
● Retentivity preset Yes
Local data
● per priority class, max. 32 kbyte; Max. 2 KB per block
Address area
I/O address area
● Inputs 2 048 byte
● Outputs 2 048 byte
of which distributed
— Inputs 2 048 byte
— Outputs 2 048 byte
Process image
● Inputs 2 048 byte
● Outputs 2 048 byte
● Inputs, adjustable 2 048 byte
● Outputs, adjustable 2 048 byte
● Inputs, default 384 byte
● Outputs, default 384 byte
Subprocess images
● Number of subprocess images, max. 1
Digital channels
● Inputs 16 384
— of which central 1 024
● Outputs 16 384
— of which central 1 024
Analog channels
● Inputs 1 024
— of which central 256
● Outputs 1 024
— of which central 256
Hardware configuration
Number of expansion units, max. 3
Number of DP masters
● integrated 1
● via CP 4
Number of operable FMs and CPs (recommended)
● FM 8
● CP, PtP 8
● CP, LAN 10
Rack
● Racks, max. 4
● Modules per rack, max. 8
Time of day
Clock
● Hardware clock (real-time) Yes
● retentive and synchronizable Yes
● Backup time 6 wk; At 40 °C ambient temperature
● Deviation per day, max. 10 s; Typ.: 2 s
● Behavior of the clock following POWER-ON Clock continues running after POWER OFF
● Behavior of the clock following expiry of backup period Clock continues to run with the time at which the power failure occurred
Operating hours counter
● Number 1
● Number/Number range 0
● Range of values 0 to 2^31 hours (when using SFC 101)
● Granularity 1 hour
● retentive Yes; Must be restarted at each restart
Clock synchronization
● supported Yes
● to MPI, master Yes
● to MPI, slave Yes
● to DP, master Yes; With DP slave only slave clock
● to DP, slave Yes
● in AS, master Yes
● in AS, slave No
Digital inputs
Number of digital inputs 0
Digital outputs
Number of digital outputs 0
Analog inputs
Number of analog inputs 0
Analog outputs
Number of analog outputs 0
Interfaces
Number of industrial Ethernet interfaces 0
Number of PROFINET interfaces 0
Number of RS 485 interfaces 2
Number of RS 422 interfaces 0
1. Interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated No
Power supply to interface (15 to 30 V DC), max. 200 mA
Functionality
● MPI Yes
● PROFIBUS DP master No
● PROFIBUS DP slave No
● Point-to-point connection No
MPI
● Transmission rate, max. 187.5 kbit/s
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication Yes
— S7 basic communication Yes
— S7 communication Yes; Only server, configured on one side
— S7 communication, as client No
— S7 communication, as server Yes
2. Interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated Yes
Power supply to interface (15 to 30 V DC), max. 200 mA
Functionality
● MPI No
● PROFIBUS DP master Yes
● PROFIBUS DP slave Yes
● Point-to-point connection No
DP master
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 124; Per station
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication Yes; I blocks only
— S7 communication Yes; Only server, configured on one side
— S7 communication, as client No
— S7 communication, as server Yes
— Equidistance Yes
— Isochronous mode Yes; OB 61
— SYNC/FREEZE Yes
— Activation/deactivation of DP slaves Yes
— Number of DP slaves that can be simultaneously activated/deactivated, max. 8
— DPV1 Yes
Address area
— Inputs, max. 2 048 byte
— Outputs, max. 2 048 byte
User data per DP slave
— Inputs, max. 244 byte
— Outputs, max. 244 byte
DP slave
● GSD file The latest GSD file is available at: http://www.siemens.com/profibus-gsd
● Transmission rate, max. 12 Mbit/s
● automatic baud rate search Yes; only with passive interface
● Address area, max. 32
● User data per address area, max. 32 byte
Services
— PG/OP communication Yes
— Routing Yes; Only with active interface
— Global data communication No
— S7 basic communication No
— S7 communication Yes; Only server, configured on one side
— S7 communication, as client No
— S7 communication, as server Yes
— Direct data exchange (slave-to-slave communication) Yes
— DPV1 No
Transfer memory
— Inputs 244 byte
— Outputs 244 byte
Isochronous mode
Isochronous operation (application synchronized up to terminal) Yes
Communication functions
PG/OP communication Yes
Data record routing Yes
Global data communication
● supported Yes
● Number of GD loops, max. 8
● Number of GD packets, max. 8
● Number of GD packets, transmitter, max. 8
● Number of GD packets, receiver, max. 8
● Size of GD packets, max. 22 byte
● Size of GD packet (of which consistent), max. 22 byte
S7 basic communication
● supported Yes
● User data per job, max. 76 byte
● User data per job (of which consistent), max. 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)
S7 communication
● supported Yes
● as server Yes
● as client Yes; Via CP and loadable FB
● User data per job, max. 180 byte; With PUT/GET
● User data per job (of which consistent), max. 240 byte; as server
S5 compatible communication
● supported Yes; via CP and loadable FC
Number of connections
● overall 16
● usable for PG communication 15
— reserved for PG communication 1
— adjustable for PG communication, min. 1
— adjustable for PG communication, max. 15
● usable for OP communication 15
— reserved for OP communication 1
— adjustable for OP communication, min. 1
— adjustable for OP communication, max. 15
● usable for S7 basic communication 12
— reserved for S7 basic communication 0
— adjustable for S7 basic communication, min. 0
— adjustable for S7 basic communication, max. 12
S7 message functions
Number of login stations for message functions, max. 16; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 300
Test commissioning functions
Status block Yes; Up to 2 simultaneously
Single step Yes
Number of breakpoints 4
Status/control
● Status/control variable Yes
● Variables Inputs, outputs, memory bits, DB, times, counters
● Number of variables, max. 30
— of which status variables, max. 30
— of which control variables, max. 14
Forcing
● Forcing Yes
● Forcing, variables Inputs, outputs
● Number of variables, max. 10
Diagnostic buffer
● present Yes
● Number of entries, max. 500
— adjustable No
— of which powerfail-proof 100; Only the last 100 entries are retained
● Number of entries readable in RUN, max.
— can be set Yes; From 10 to 499
— preset 10
Service data
● can be read out Yes
Ambient conditions
Ambient temperature during operation
● min. 0 °C
● max. 60 °C
Configuration
Configuration software
● STEP 7 Yes; V5.2 SP1 or higher with HW update
Programming
● Command set see instruction list
● Nesting levels 8
● System functions (SFC) see instruction list
● System function blocks (SFB) see instruction list
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— CFC Yes
— GRAPH Yes
— HiGraph® Yes
Know-how protection
● User program protection/password protection Yes
● Block encryption Yes; With S7 block Privacy
Dimensions
Width 40 mm
Height 125 mm
Depth 130 mm
Weights
Weight 290 g