Simatic DP, Electronics Module, 2AI I high feature for ET 200S, W15mm, cycle time per module: 0.5ms, ±20mA, 15bit+sign, 4..20mA, 15bit, operational limit ±0.1%, SF LED (group fault), Siemens
Image is illustrative
Simatic DP, Electronics Module, 2AI I high feature for ET 200S, W15mm, cycle time per module: 0.5ms, ±20mA, 15bit+sign, 4..20mA, 15bit, operational limit ±0.1%, SF LED (group fault), Siemens
Code: 6ES7134-4MB02-0AB0
Price (indicative)
402,90 €  /pc
Manufacturer :
Availability:
21 days
Weight:
0.0473 kg/pc
Volume:
0.0001 m3/pc
 

Simatic DP, Electronics Module, 2AI I high feature for ET 200S, W15mm, cycle time per module: 0.5ms, ±20mA, 15bit+sign, 4..20mA, 15bit, operational limit ±0.1%, SF LED (group fault), Siemens

SIMATIC DP, Electronics module 2 AI I High Feature for ET 200S, 15 mm width, Cycle time per module: 0.5 ms, +/-20mA; 15 bit+sign, 4.. 20mA; 15 bit, Operational limit +/-0.1% with SF LED (group fault)
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 48 mA
from backplane bus 3.3 V DC, max. 10 mA
Output voltage
Power supply to the transmitters
● present Yes
● short-circuit proof Yes
Power loss
Power loss, typ. 1.2 W
Address area
Address space per module
● Address space per module, max. 4 byte
Analog inputs
Number of analog inputs 2
permissible input current for current input (destruction limit), max. 50 mA
Cycle time (all channels) max. 0.5 ms; 0.5 ms for 2 channels without noise suppression, 18 / 21 ms per channel with noise suppression
Input ranges (rated values), currents
● -20 mA to +20 mA Yes
● 4 mA to 20 mA Yes
Cable length
● shielded, max. 200 m
Analog value generation for the inputs
Measurement principle Sigma Delta
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Interference voltage suppression for interference frequency f1 in Hz 60 / 50 Hz / no
● Conversion time (per channel) 0.04 ms; Without noise suppression 17/20 ms per channel with error
Smoothing of measured values
● parameterizable Yes; In 4 stages: 1x, 4x, 16x, 32x cycle time
● Step: None Yes; 1x
● Step: low Yes; 4x
● Step: Medium Yes; 16x
● Step: High Yes; 32x
Encoder
Connection of signal encoders
● for current measurement as 2-wire transducer
— Burden of 2-wire transmitter, max. 750 Ω
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.03 %
Temperature error (relative to input range), (+/-) 0.003 %/K
Crosstalk between the inputs, min. -100 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.01 %
Operational error limit in overall temperature range
● Current, relative to input range, (+/-) 0.1 %; 0.2% without interference frequency suppression
Basic error limit (operational limit at 25 °C)
● Current, relative to input range, (+/-) 0.05 %; 0.1% without interference frequency suppression
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 90 dB
● Common mode interference (USS < 2.5 V) , min. 100 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal) Yes
Interrupts/diagnostics/status information
Alarms
● Hardware interrupt Yes
Diagnostic messages
● Wire-break Yes; Measuring range 4 to 20 mA only
● Group error Yes
● Overflow/underflow Yes
Diagnostics indication LED
● Group error SF (red) Yes
Parameter
Remark 12 bytes, 4 bytes in compatibility mode
Diagnostics wire break Disable / enable
Measurement type/range deactivated / ±20 mA / 4 to 20 mA
Group diagnostics Disable / enable
Overflow/underflow Disable / enable
Potential separation
Potential separation analog inputs
● between the channels No; however, increased permissible potential difference between the inputs.
● between the channels and backplane bus Yes
● Between the channels and load voltage L+ Yes
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 45 g