Image is illustrative
|
Simatic ET 200SP, Digital Input Module, 8DI 24VDC, type 3 (IEC 61131), sink input, (PNP, P-reading), fits BU-type A0, color code CC01, input delay time 0.05..20ms, module diagnostics for short-circuiting of sensor supply, Draht break, supply voltage, Code:
6ES7131-6BF01-0BA0
Price (indicative)
Manufacturer
:
Availability:
21 days
|
Weight:
0.0389 kg/pc
|
Volume:
0.0001 m3/pc
|
|
|
|
|
Simatic ET 200SP, Digital Input Module, 8DI 24VDC, type 3 (IEC 61131), sink input, (PNP, P-reading), fits to BU-type A0, colour code CC01, input delay time 0.05..20ms, module diagnostics for: short-circuit of sensor supply, wire break, supply voltage, SieSIMATIC ET 200SP, Digital input module, DI 8x 24V DC Standard, type 3 (IEC 61131), sink input, (PNP, P-reading), Packing unit: 1 piece, fits to BU-type A0, Colour Code CC01, input delay time 0,05..20ms, module diagnostics for: short-circuit of sensor supply, wire break, supply voltage
General information |
Product type designation |
DI 8x24 VDC ST |
Firmware version |
V0.0 |
● FW update possible |
No |
usable BaseUnits |
BU type A0 |
Color code for module-specific color identification plate |
CC01 |
Product function |
● I&M data |
Yes; I&M0 to I&M3 |
Engineering with |
● STEP 7 TIA Portal configurable/integrated as of version |
V14 |
● STEP 7 configurable/integrated as of version |
V5.5 SP3 or higher |
● PCS 7 configurable/integrated as of version |
V8.1 SP1 |
● PROFIBUS as of GSD version/GSD revision |
One GSD file each, Revision 3 and 5 and higher |
● PROFINET as of GSD version/GSD revision |
GSDML V2.3 |
Operating mode |
● DI |
Yes |
● Counter |
No |
● Oversampling |
No |
● MSI |
No |
Supply voltage |
Rated value (DC) |
24 V |
permissible range, lower limit (DC) |
19.2 V |
permissible range, upper limit (DC) |
28.8 V |
Reverse polarity protection |
Yes |
Input current |
Current consumption, max. |
50 mA; All channels are supplied from the encoder supply |
Encoder supply |
Number of outputs |
8 |
Output voltage encoder supply, min. |
19.2 V |
Short-circuit protection |
Yes; per module |
24 V encoder supply |
● 24 V |
Yes |
● Short-circuit protection |
Yes |
● Output current, max. |
700 mA; Total current of all encoders |
● Output current per channel, max. |
700 mA |
● Output current per module, max. |
700 mA |
Power loss |
Power loss, typ. |
1 W; 24 V, 8 inputs supplied via encoder supply |
Address area |
Address space per module |
● Inputs |
1 byte; + 1 byte for QI information |
Hardware configuration |
Automatic encoding |
Yes |
● Mechanical coding element |
Yes |
Submodules |
● Number of configurable submodules, max. |
4 |
Selection of BaseUnit for connection variants |
● 1-wire connection |
BU type A0 |
● 2-wire connection |
BU type A0 |
● 3-wire connection |
BU type A0 with AUX terminals |
● 4-wire connection |
BU type A0 + Potential isolation module |
Digital inputs |
Number of digital inputs |
8 |
Digital inputs, parameterizable |
Yes |
Source/sink input |
P-reading |
Input characteristic curve in accordance with IEC 61131, type 3 |
Yes |
Input voltage |
● Type of input voltage |
DC |
● Rated value (DC) |
24 V |
● for signal "0" |
-30 to +5V |
● for signal "1" |
+11 to +30V |
Input current |
● for signal "1", typ. |
2.5 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— parameterizable |
Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 to 500 µs, depending on line length) |
— at "0" to "1", min. |
0.05 ms |
— at "0" to "1", max. |
20 ms |
— at "1" to "0", min. |
0.05 ms |
— at "1" to "0", max. |
20 ms |
Cable length |
● shielded, max. |
1 000 m |
● unshielded, max. |
600 m |
Encoder |
Connectable encoders |
● 2-wire sensor |
Yes |
— permissible quiescent current (2-wire sensor), max. |
1.5 mA |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
No |
Interrupts/diagnostics/status information |
Diagnostics function |
Yes |
Alarms |
● Diagnostic alarm |
Yes |
Diagnostic messages |
● Diagnostic information readable |
Yes |
● Monitoring the supply voltage |
Yes |
— parameterizable |
Yes |
● Monitoring of encoder power supply |
Yes; Module-by-module, optional protective circuit for preventing wire-break diagnostics in the case of simple encoder contacts: 25 kOhm to 45 kOhm |
● Wire-break |
Yes; Module-wise |
● Short-circuit |
Yes; Module-wise |
Diagnostics indication LED |
● Monitoring of the supply voltage (PWR-LED) |
Yes; green PWR LED |
● Channel status display |
Yes; Green LED |
● for channel diagnostics |
No |
● for module diagnostics |
Yes; green/red DIAG LED |
Potential separation |
Potential separation channels |
● between the channels |
No |
● between the channels and backplane bus |
Yes |
● between the channels and the power supply of the electronics |
No |
Isolation |
Isolation tested with |
707 V DC (type test) |
Ambient conditions |
Ambient temperature during operation |
● horizontal installation, min. |
0 °C |
● horizontal installation, max. |
60 °C |
● vertical installation, min. |
0 °C |
● vertical installation, max. |
50 °C |
Altitude during operation relating to sea level |
● Ambient air temperature-barometric pressure-altitude |
On request: Ambient temperatures lower than 0 °C (without condensation) and/or installation altitudes greater than 2 000 m |
Dimensions |
Width |
15 mm |
Height |
73 mm |
Depth |
58 mm |
Weights |
Weight, approx. |
28 g |
last modified: |
11/10/2018 |
|
File description
|
File type
|