SITOP select Diagnostics module 4-channel input: 24 V DC/40 A output: 24 V DC/4x 10 A Level adjustable 2-10 A |
Input |
Type of the power supply network |
Controlled DC voltage (SITOP select is not designed for operation with DC UPS module 40 A (6EP1 931-2FC21/-2FC42) |
Supply voltage / at DC / Rated value |
24 V |
Input voltage / at DC |
22 ... 30 V |
Overvoltage overload capability |
35 V; 100 ms |
Input current / at rated input voltage 24 V / Rated value |
40 A |
Output |
Voltage curve / at output |
controlled DC voltage |
Formula for output voltage |
Vin - approx. 0.3 V |
Relative overall tolerance / of the voltage / Note |
In accordance with the supplying input voltage |
Number of outputs |
4 |
Output current / up to 60 °C / per output / rated value |
10 A |
Adjustable pick-up value current / of the current-dependent overload release |
2 ... 10 A |
Type of response value setting |
via potentiometer |
Product feature / parallel switching of outputs |
No |
Product feature / bridging of equipments |
Yes |
Type of outputs connection |
Simultaneous connection of all outputs after power up of the supply voltage, delay time of 24 ms or 100 ms programmable for sequential connection |
Efficiency |
Efficiency in percent |
97 % |
Power loss [W] / at rated output current / for rated value of the output current / typical |
30 W |
Switch-off characteristic per output |
Switching characteristic |
|
● of the excess current |
Iout = 1.0 ...1.3 x set value, switch-off after approx. 5 s |
● of the current limitation |
Iout = 1.3 x set value, switch-off after approx. 50 ... 100 ms |
● of the immediate switch-off |
Iout > set value and Vin < 20 V, switch-off after approx. 0.5 ms |
Residual current at switch-off / typical |
20 mA |
Design of the reset device/resetting mechanism |
Using keys on the module |
Remote reset function |
- |
Protection and monitoring |
Fuse protection type / at input |
Blade-type fuse per output (equipped when delivered with 15 A fuse) |
Display version / for normal operation |
Two-color LED per output: green LED for "Output switched through"; red LED for "Output switched off due to overcurrent" |
Design of the switching contact / for signaling function |
Common signal contact (NO contact, rating 0.5 A/24 V DC) |
Safety |
Galvanic isolation / between input and output at switch-off |
No |
Operating resource protection class |
Class III |
Certificate of suitability |
|
● CE marking |
Yes |
● as approval for USA |
UL-Recognized (UL 2367) File E328600; cULus-Listed (UL 508, CSA C22.2 No. 107.1) File E197259; cURus (UL 60950, CSA C22.2 No. 60950) File E151273 |
Standard / for safety |
according to EN 60950-1 and EN 50178 |
Certificate of suitability / relating to ATEX |
ATEX (EX) II 3G Ex nAC IIC T4 U; cCSAus Class I, Div. 2, Group ABCD, T4 |
Protection class IP |
IP20 |
EMC |
Standard |
|
● for emitted interference |
EN 55022 Class B |
● for interference immunity |
EN 61000-6-2 |
Operating data |
Ambient temperature |
|
● during operation |
0 ... 60 °C |
— Note |
with natural convection |
● during transport |
-40 ... +85 °C |
● during storage |
-40 ... +85 °C |
Environmental category / acc. to IEC 60721 |
Climate class 3K3, no condensation |
Mechanics |
Type of electrical connection |
screw-type terminals |
● at input |
+24 V: 2 screw terminals for 0.5 ... 16 mm²; 0 V: 2 screw terminals for 0.5 ... 4 mm² |
● at output |
Output 1 ... 4: 1 screw terminal each for 0.22 ... 4 mm² |
● for signaling contact |
2 screw terminals for 0.22 ... 4 mm² |
● for auxiliary contacts |
- |
Width / of the enclosure |
72 mm |
Height / of the enclosure |
90 mm |
Depth / of the enclosure |
90 mm |
Installation width |
72 mm |
Mounting height |
190 mm |
Net weight |
0.4 kg |
Mounting type |
Snaps onto DIN rail EN 60715 35x7.5/15 |
Product component / belonging to |
4x blade-type fuse 15 A |
MTBF / at 40 °C |
378 928 h |
Other information |