ISO Cylinder DSBG-160-170-PPVA-N3, Festo
ISO Cylinder DSBG-160-170-PPVA-N3, Festo



Siplus S7-300 SM322 32DO, 40P, -25..70°C w. conformal coating, conformity w. EN50155 T1 KAT 1 KL A/B, based on 6ES7322-1BL00-0AA0, digital output SM322, optically isolated, 32DO, 24VDC, 0.5A, 40pin, output currents 4A/group (16A/module), Siemens
Image is illustrative
Siplus S7-300 SM322 32DO, 40P, -25..70°C w. conformal coating, conformity w. EN50155 T1 KAT 1 KL A/B, based on 6ES7322-1BL00-0AA0, digital output SM322, optically isolated, 32DO, 24VDC, 0.5A, 40pin, output currents 4A/group (16A/module), Siemens
Code: 6AG1322-1BL00-2AA0
Price (indicative)
1.526,00 €  /pc
Manufacturer :
Availability:
ask for dd
Weight:
0.336 kg/pc
Volume:
0.0011 m3/pc
 

Siplus S7-300 SM322 32DO, 40P, -25..70°C w. conformal coating, conformity w. EN50155 T1 KAT 1 KL A/B, based on 6ES7322-1BL00-0AA0, digital output SM322, optically isolated, 32DO, 24VDC, 0.5A, 40pin, output currents 4A/group (16A/module), Siemens

Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 20.4 V
● permissible range, upper limit (DC) 28.8 V
Input current
from load voltage L+ (without load), max. 160 mA
from backplane bus 5 V DC, max. 110 mA
Power loss
Power loss, typ. 6.6 W
Digital outputs
Number of digital outputs 32
Limitation of inductive shutdown voltage to L+ (-53 V)
Switching capacity of the outputs
● on lamp load, max. 5 W
Load resistance range
● lower limit 48 Ω
● upper limit 4 kΩ
Output voltage
● for signal "1", min. L+ (-0.8 V)
Output current
● for signal "1" rated value 0.5 A
● for signal "1" minimum load current 5 mA
● for signal "0" residual current, max. 0.5 mA
Switching frequency
● with resistive load, max. 100 Hz
● on lamp load, max. 10 Hz
Total current of the outputs (per group)
horizontal installation
— up to 40 °C, max. 4 A
— up to 60 °C, max. 3 A
— up to 70 °C, max. 2 A
vertical installation
— up to 40 °C, max. 2 A
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Interrupts/diagnostics/status information
Diagnostic functions No
Alarms
● Diagnostic alarm No
Diagnostic messages
● Wire-break No
● Short-circuit No
● missing load voltage No
Diagnostics indication LED
● Rated load voltage PWR (green) No
● Fuse OK FSG (green) No
● Group error SF (red) No
● Status indicator digital output (green) Yes; per channel
● Channel fault indicator F (red) No
Potential separation
Potential separation digital outputs
● between the channels Yes
● between the channels, in groups of 8
● between the channels and backplane bus Yes; Optocoupler
Permissible potential difference
between different circuits 75 V DC/60 V AC
Isolation
Isolation tested with 500 V DC
Standards, approvals, certificates
CE mark Yes
UL approval Yes; File E239877
FM approval Yes; CofC 3028431
RCM (formerly C-TICK) Yes
KC approval Yes
EAC (formerly Gost-R) Yes
Railway application
● EN 50155 Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class A/B
Ambient conditions
Ambient temperature during operation
● min. -25 °C; = Tmin
● max. 70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/ULhaz/ATEX/FM use applies
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Altitude during operation relating to sea level
● Ambient air temperature-barometric pressure-altitude Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
● With condensation, tested in accordance with IEC 60068-2-38, max. 100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3 Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3 Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
— to mechanically active substances according to EN 60721-3-3 Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Connection method
required front connector 40-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 120 mm
Weights
Weight 260 g
last modified: 11/20/2017
 
 
AIS.Hensch | e-mail: info@ais-deutschland.de | +49 (0) 511-69608385 | 2021 ©


 