Isolation Amplifier MACX MCR-SL-NAM-R-SP, Phoenix
Image is illustrative
Isolation Amplifier MACX MCR-SL-NAM-R-SP, Phoenix
Code: 2924252
Price
194,60 €  /pc
Manufacturer :
Availability:
21 days
Weight:
0.1593 kg/pc
Volume:
0.0002 m3/pc
 

Isolation Amplifier MACX MCR-SL-NAM-R-SP, Phoenix

Note

Utilization restriction EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width 12.5 mm
Height 116 mm
Depth 113.7 mm
114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715)

Ambient conditions

Ambient temperature (operation) -40 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)
Degree of protection IP20 (not assessed by UL)
Noise immunity EN 61000-6-2 EN 61326
Altitude ≤ 2000 m
Ambient temperature (operation) -40 °C ... 60 °C
Rated insulation voltage 320 V (Power supply, input / output)
Altitude ≤ 3000 m
Ambient temperature (operation) -40 °C ... 54 °C
Rated insulation voltage 190 V (Power supply, input / output)
Altitude ≤ 4000 m
Ambient temperature (operation) -40 °C ... 48 °C
Rated insulation voltage 63 V (Power supply, input / output)
Altitude ≤ 5000 m
Ambient temperature (operation) -40 °C ... 42 °C
Rated insulation voltage 63 V (Power supply, input / output)

Input data

Non-load voltage ~ 8 V DC
Switching points (attenuated) < 1.2 mA (blocking)
Switching points (unattenuated) > 2.1 mA (conductive)
Available input sources NAMUR proximity sensors (IEC/EN 60947-5-6)
Short-circuit current ~ 8 mA
Switching hysteresis < 0.2 mA
Line fault detection Break 0.05 mA < IIN < 0.35 mA
Short circuit 100 Ω < RSensor < 360 Ω

Output data

Switching output Relay output
Contact type 1 changeover contact
Contact material AgSnO2, hard gold-plated
Maximum switching voltage 250 V AC (2 A)
120 V DC (0.2 A)
30 V DC (2 A)
Maximum switching capacity 500 VA
Mechanical service life 107 cycles
Switching frequency ≤ 20 Hz (without load)

Power supply

Nominal supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
Max. current consumption 21 mA (24 V DC)
Power dissipation < 650 mW
Power consumption < 650 mW

Connection data

Connection method Push-in connection
Stripping length 8 mm
Conductor cross section solid 0.2 mm² ... 1.5 mm²
Conductor cross section flexible 0.2 mm² ... 1.5 mm²
Conductor cross section AWG 24 ... 16

General

No. of channels 1
Status display Green LED (supply voltage)
LED yellow (switching state)
Red LED (line errors)
Electromagnetic compatibility Conformance with EMC directive
Interference emission EN 61000-6-4
Housing material PA 6.6-FR
Color gray
Designation Input/output
Electrical isolation 375 V (Peak value in accordance with IEC/EN 60079-11)
Overvoltage category II
Degree of pollution 2
Altitude ≤ 2000 m
Designation Input/output/supply, DIN rail connector
Rated insulation voltage 300 Vrms
Test voltage 2.5 kV AC (50 Hz, 1 min.)
Overvoltage category II
Degree of pollution 2
Insulation Safe isolation in accordance with IEC/EN 61010-1
Altitude ≤ 2000 m
Designation Output/input, supply, TBUS
Rated insulation voltage 300 Vrms
Test voltage 2.5 kV AC (50 Hz, 1 min.)
Overvoltage category III
Degree of pollution 2
Insulation Safe isolation in accordance with IEC/EN 61010-1
Altitude ≤ 2000 m
Designation Input/supply, DIN rail connector
Electrical isolation 375 V (Peak value in accordance with IEC/EN 60079-11)
Overvoltage category II
Degree of pollution 2
Altitude ≤ 2000 m

Safety characteristic data

Integrity requirement IEC 61508 - Low demand
Designation Non-inverted operation
Equipment type Type A
Safety Integrity Level (SIL) 2
Safe Failure Fraction (SFF) 78 %
λSU 2.49 x 10-7 (249 FIT)
λSD 6 x 10-9 (6 FIT)
λDU 6.4 x 10-8 (64 FIT)
λDD 7 x 10-9 (7 FIT)
Probability of a hazardous failure on demand (PFDAVG) 3.09 x 10-4 (1 year)
6.17 x 10-4 (2 years)
1.54 x 10-3 (5 years)
Diagnostic coverage (DC) DCS = 2.4 %, DCD = 9 %
Integrity requirement IEC 61508 - Low demand
Designation Inverted operation
Equipment type Type A
Safety Integrity Level (SIL) 2
Safe Failure Fraction (SFF) 78 %
λSU 2.48 x 10-7 (248 FIT)
λSD 1 x 10-9 (1 FIT)
λDU 6.2 x 10-8 (62 FIT)
λDD 6 x 10-9 (6 FIT)
Probability of a hazardous failure on demand (PFDAVG) 3.01 x 10-4 (1 year)
6.02 x 10-4 (2 years)
1.5 x 10-3 (5 years)
Diagnostic coverage (DC) DCS = 0.4 %, DCD = 8 %
Safety Integrity Level (SIL) 2

Standards and Regulations

Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Designation GB Standard
Standards/regulations GB 3836.1
GB 3836.8

Conformance/approvals

Designation CE
Certificate CE-compliant
Additional text and EN 61326-1
Designation ATEX
Identification  II 3 G Ex ec nC IIC T4 Gc
Certificate IBExU 07 ATEX 1069 X
Designation IECEx
Identification Ex ec nC IIC T4 Gc
Certificate IBE 08.0001 X
Designation CCC / China-Ex
Identification Ex nA nC IIC T4 Gc
Designation UL, USA/Canada
Identification UL 508 Listed
UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Groups IIC, IIB, IIA T4
Designation UL, USA/Canada
Identification UL 508 Listed
UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC T4
Designation Shipbuilding approval
Certificate DNV GL TAA00000AG
Designation Safety Integrity Level (SIL, IEC 61508)
Identification 2
Temperature B
Humidity B
Vibration A
EMC B
Enclosure Required protection according to the Rules shall be provided upon installation on board

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

ECLASS

ECLASS 10.0.1 27210121
ECLASS 11.0 27210121
ECLASS 4.0 27210100
ECLASS 4.1 27210100
ECLASS 5.0 27210100
ECLASS 5.1 27210100
ECLASS 6.0 27210100
ECLASS 7.0 27210121
ECLASS 9.0 27210121

ETIM

ETIM 2.0 EC001485
ETIM 3.0 EC001485
ETIM 4.0 EC001485
ETIM 6.0 EC001485
ETIM 7.0 EC001485

UNSPSC

UNSPSC 6.01 30211506
UNSPSC 7.0901 39121008
UNSPSC 11 39121008
UNSPSC 12.01 39121008
UNSPSC 13.2 39121008
UNSPSC 18.0 39121008
UNSPSC 19.0 39121008
UNSPSC 20.0 39121008
UNSPSC 21.0 39121008
 
 
AIS.Hensch | e-mail: info@ais-deutschland.de | +49 (0) 511-69608385 | 2021 ©


 
X
 
X