Image is illustrative
|
Isolation Amplifier MACX MCR-SL-NAM-R-SP, Phoenix Code:
2924252
Price
Manufacturer
:
Availability:
21 days
|
Weight:
0.1593 kg/pc
|
Volume:
0.0002 m3/pc
|
|
|
|
|
Isolation Amplifier MACX MCR-SL-NAM-R-SP, PhoenixNote
Utilization restriction
|
EMC: class A product, see manufacturer's declaration in the download area
|
Dimensions
Width
|
12.5 mm
|
Height
|
116 mm
|
Depth
|
113.7 mm
|
|
114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715)
|
Ambient conditions
Ambient temperature (operation)
|
-40 °C ... 60 °C (Any mounting position)
|
Ambient temperature (storage/transport)
|
-40 °C ... 85 °C
|
Permissible humidity (operation)
|
10 % ... 95 % (non-condensing)
|
Permissible humidity (storage/transport)
|
5 % ... 95 % (non-condensing)
|
Degree of protection
|
IP20 (not assessed by UL)
|
Noise immunity
|
EN 61000-6-2 EN 61326
|
Altitude
|
≤ 2000 m
|
Ambient temperature (operation)
|
-40 °C ... 60 °C
|
Rated insulation voltage
|
320 V (Power supply, input / output)
|
Altitude
|
≤ 3000 m
|
Ambient temperature (operation)
|
-40 °C ... 54 °C
|
Rated insulation voltage
|
190 V (Power supply, input / output)
|
Altitude
|
≤ 4000 m
|
Ambient temperature (operation)
|
-40 °C ... 48 °C
|
Rated insulation voltage
|
63 V (Power supply, input / output)
|
Altitude
|
≤ 5000 m
|
Ambient temperature (operation)
|
-40 °C ... 42 °C
|
Rated insulation voltage
|
63 V (Power supply, input / output)
|
Input data
Non-load voltage
|
~ 8 V DC
|
Switching points (attenuated)
|
< 1.2 mA (blocking)
|
Switching points (unattenuated)
|
> 2.1 mA (conductive)
|
Available input sources
|
NAMUR proximity sensors (IEC/EN 60947-5-6)
|
Short-circuit current
|
~ 8 mA
|
Switching hysteresis
|
< 0.2 mA
|
Line fault detection
|
Break 0.05 mA < IIN < 0.35 mA
|
|
Short circuit 100 Ω < RSensor < 360 Ω
|
Output data
Switching output
|
Relay output
|
Contact type
|
1 changeover contact
|
Contact material
|
AgSnO2, hard gold-plated
|
Maximum switching voltage
|
250 V AC (2 A)
|
|
120 V DC (0.2 A)
|
|
30 V DC (2 A)
|
Maximum switching capacity
|
500 VA
|
Mechanical service life
|
107 cycles
|
Switching frequency
|
≤ 20 Hz (without load)
|
Power supply
Nominal supply voltage
|
24 V DC
|
Supply voltage range
|
19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
|
Max. current consumption
|
21 mA (24 V DC)
|
Power dissipation
|
< 650 mW
|
Power consumption
|
< 650 mW
|
Connection data
Connection method
|
Push-in connection
|
Stripping length
|
8 mm
|
Conductor cross section solid
|
0.2 mm² ... 1.5 mm²
|
Conductor cross section flexible
|
0.2 mm² ... 1.5 mm²
|
Conductor cross section AWG
|
24 ... 16
|
General
No. of channels
|
1
|
Status display
|
Green LED (supply voltage)
|
|
LED yellow (switching state)
|
|
Red LED (line errors)
|
Electromagnetic compatibility
|
Conformance with EMC directive
|
Interference emission
|
EN 61000-6-4
|
Housing material
|
PA 6.6-FR
|
Color
|
gray
|
Designation
|
Input/output
|
Electrical isolation
|
375 V (Peak value in accordance with IEC/EN 60079-11)
|
Overvoltage category
|
II
|
Degree of pollution
|
2
|
Altitude
|
≤ 2000 m
|
Designation
|
Input/output/supply, DIN rail connector
|
Rated insulation voltage
|
300 Vrms
|
Test voltage
|
2.5 kV AC (50 Hz, 1 min.)
|
Overvoltage category
|
II
|
Degree of pollution
|
2
|
Insulation
|
Safe isolation in accordance with IEC/EN 61010-1
|
Altitude
|
≤ 2000 m
|
Designation
|
Output/input, supply, TBUS
|
Rated insulation voltage
|
300 Vrms
|
Test voltage
|
2.5 kV AC (50 Hz, 1 min.)
|
Overvoltage category
|
III
|
Degree of pollution
|
2
|
Insulation
|
Safe isolation in accordance with IEC/EN 61010-1
|
Altitude
|
≤ 2000 m
|
Designation
|
Input/supply, DIN rail connector
|
Electrical isolation
|
375 V (Peak value in accordance with IEC/EN 60079-11)
|
Overvoltage category
|
II
|
Degree of pollution
|
2
|
Altitude
|
≤ 2000 m
|
Safety characteristic data
Integrity requirement
|
IEC 61508 - Low demand
|
Designation
|
Non-inverted operation
|
Equipment type
|
Type A
|
Safety Integrity Level (SIL)
|
2
|
Safe Failure Fraction (SFF)
|
78 %
|
λSU
|
2.49 x 10-7 (249 FIT)
|
λSD
|
6 x 10-9 (6 FIT)
|
λDU
|
6.4 x 10-8 (64 FIT)
|
λDD
|
7 x 10-9 (7 FIT)
|
Probability of a hazardous failure on demand (PFDAVG)
|
3.09 x 10-4 (1 year)
|
|
6.17 x 10-4 (2 years)
|
|
1.54 x 10-3 (5 years)
|
Diagnostic coverage (DC)
|
DCS = 2.4 %, DCD = 9 %
|
Integrity requirement
|
IEC 61508 - Low demand
|
Designation
|
Inverted operation
|
Equipment type
|
Type A
|
Safety Integrity Level (SIL)
|
2
|
Safe Failure Fraction (SFF)
|
78 %
|
λSU
|
2.48 x 10-7 (248 FIT)
|
λSD
|
1 x 10-9 (1 FIT)
|
λDU
|
6.2 x 10-8 (62 FIT)
|
λDD
|
6 x 10-9 (6 FIT)
|
Probability of a hazardous failure on demand (PFDAVG)
|
3.01 x 10-4 (1 year)
|
|
6.02 x 10-4 (2 years)
|
|
1.5 x 10-3 (5 years)
|
Diagnostic coverage (DC)
|
DCS = 0.4 %, DCD = 8 %
|
Safety Integrity Level (SIL)
|
2
|
Standards and Regulations
Electromagnetic compatibility
|
Conformance with EMC directive
|
Noise emission
|
EN 61000-6-4
|
Designation
|
GB Standard
|
Standards/regulations
|
GB 3836.1
|
|
GB 3836.8
|
Conformance/approvals
Designation
|
CE
|
Certificate
|
CE-compliant
|
Additional text
|
and EN 61326-1
|
Designation
|
ATEX
|
Identification
|
II 3 G Ex ec nC IIC T4 Gc
|
Certificate
|
IBExU 07 ATEX 1069 X
|
Designation
|
IECEx
|
Identification
|
Ex ec nC IIC T4 Gc
|
Certificate
|
IBE 08.0001 X
|
Designation
|
CCC / China-Ex
|
Identification
|
Ex nA nC IIC T4 Gc
|
Designation
|
UL, USA/Canada
|
Identification
|
UL 508 Listed
|
|
UL 61010 Listed
|
|
Class I, Div. 2, Groups A, B, C, D T4
|
|
Class I, Zone 2, Groups IIC, IIB, IIA T4
|
Designation
|
UL, USA/Canada
|
Identification
|
UL 508 Listed
|
|
UL 61010 Listed
|
|
Class I, Div. 2, Groups A, B, C, D T4
|
|
Class I, Zone 2, Group IIC T4
|
Designation
|
Shipbuilding approval
|
Certificate
|
DNV GL TAA00000AG
|
Designation
|
Safety Integrity Level (SIL, IEC 61508)
|
Identification
|
2
|
Temperature
|
B
|
Humidity
|
B
|
Vibration
|
A
|
EMC
|
B
|
Enclosure
|
Required protection according to the Rules shall be provided upon installation on board
|
Environmental Product Compliance
REACh SVHC
|
Lead 7439-92-1
|
China RoHS
|
Environmentally Friendly Use Period = 50 years
|
|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
|
ECLASS
ECLASS 10.0.1 |
27210121
|
ECLASS 11.0 |
27210121
|
ECLASS 4.0 |
27210100
|
ECLASS 4.1 |
27210100
|
ECLASS 5.0 |
27210100
|
ECLASS 5.1 |
27210100
|
ECLASS 6.0 |
27210100
|
ECLASS 7.0 |
27210121
|
ECLASS 9.0 |
27210121
|
ETIM
ETIM 2.0 |
EC001485
|
ETIM 3.0 |
EC001485
|
ETIM 4.0 |
EC001485
|
ETIM 6.0 |
EC001485
|
ETIM 7.0 |
EC001485
|
UNSPSC
UNSPSC 6.01 |
30211506
|
UNSPSC 7.0901 |
39121008
|
UNSPSC 11 |
39121008
|
UNSPSC 12.01 |
39121008
|
UNSPSC 13.2 |
39121008
|
UNSPSC 18.0 |
39121008
|
UNSPSC 19.0 |
39121008
|
UNSPSC 20.0 |
39121008
|
UNSPSC 21.0 |
39121008
|
|
File description
|
File type
|