Klemmenmarkierung DEK 5/8 MM WS, PC-ABS + TPU, –40..90°C, V2, HF, Weidmüller, weiß
Klemmenmarkierung DEK 5/8 MM WS, PC-ABS + TPU, –40..90°C, V2, HF, Weidmüller, weiß



Relais REL-IR4/LDP-220DC/4X21AU, 10stk/pck, Phoenix
Image is illustrative
Relais REL-IR4/LDP-220DC/4X21AU, 10stk/pck, Phoenix
Code: 2903675
Price
161,00 €  /pk
Package 10pc, unit price 16.1EUR/pc
Manufacturer :
Availability:
21 days
Weight:
0.0353 kg/pc
Volume:
0 m3/pc
 

Relay REL-IR4/LDP-220DC/4X21AU, 10pcs/pck, Phoenix

Dimensions

Width 21.2 mm
Height 27.5 mm
Depth 35.6 mm

Ambient conditions

Ambient temperature (operation) -40 °C ... 70 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection RT I

Coil side

Nominal input voltage UN 220 V DC
Input voltage range in reference to UN
Typical input current at UN 4 mA
Typical response time 13 ms
Typical release time 14 ms
Protective circuit Damping diode
Status display Yellow LED
Power dissipation for nominal condition 0.88 W

Contact side

Contact type 4 changeover contacts
Type of switch contact Single contact
Contact material AgNi, hard gold-plated
Note If the specified maximum values for multi-layer contact relays are exceeded, the gold plating is destroyed. The maximum values of the power contact relay are then valid. This can result in a shorter service life than with a pure power contact.
Maximum switching voltage 30 V AC
36 V DC
Minimum switching voltage 2 V (At 24 mA)
Min. switching current 2 mA (24 V DC)
Maximum inrush current 50 mA
Limiting continuous current 50 mA
Interrupting rating (ohmic load) max. 1.2 W (at 24 V DC)
Switching capacity min. 48 mW
Motor load according to UL 508 1/3 HP, 240 V AC

Contact side (with destroyed gold layer)

Contact material AgNi
Note the following values are applicable if a gold layer is destroyed
Maximum switching voltage 250 V AC/DC
Minimum switching voltage 5 V (At 24 mA)
Limiting continuous current 6 A
Maximum inrush current 16 A (20 ms, N/O contacts)
Min. switching current 5 mA (at 24 V)
Interrupting rating (ohmic load) max. 144 W (at 24 V DC)
124 W (at 48 V DC)
108 W (at 60 V DC)
52 W (at 110 V DC)
48 W (at 220 V DC)
1500 VA (for 250 V AC)
Switching capacity 2 A (at 24 V, DC13)
0.22 A (at 120 V, DC13)
0.11 A (at 250 V, DC13)
1.5 A (at 24 V, AC15)
1.5 A (at 120 V, AC15)
1 A (at 240 V, AC15)

General

Test voltage 2.5 kVrms (50 Hz, 1 min., winding/contact)
2 kVrms (50 Hz, 1 min., changeover contact/changeover contact)
Operating mode 100% operating factor
Mechanical service life approx. 2x 107 cycles
Service life, electrical see diagram
Mounting position any

Connection data

Connection method Plug connection

Standards and Regulations

Connection in acc. with standard CSA
Standards/regulations IEC 60664
IEC 61810
Rated insulation voltage 250 V AC
Rated surge voltage 2.5 kV
Insulation Basic insulation
Pollution degree 2
Overvoltage category II

Conformance/approvals

Designation Corrosive gas test
Identification ISA-S71.04. G3 Harsh Group
EN 60068-2-60

Environmental Product Compliance

China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

ECLASS

ECLASS 10.0.1 27371601
ECLASS 11.0 27371601
ECLASS 4.0 27371100
ECLASS 4.1 27371100
ECLASS 5.0 27371600
ECLASS 5.1 27371600
ECLASS 6.0 27371600
ECLASS 7.0 27371601
ECLASS 9.0 27371601

ETIM

ETIM 2.0 EC001437
ETIM 3.0 EC001437
ETIM 4.0 EC001437
ETIM 6.0 EC001437
ETIM 7.0 EC001437

UNSPSC

UNSPSC 6.01 30211916
UNSPSC 7.0901 39121515
UNSPSC 11 39121515
UNSPSC 12.01 39121515
UNSPSC 13.2 39122334
UNSPSC 18.0 39122334
UNSPSC 19.0 39122334
UNSPSC 20.0 39122334
UNSPSC 21.0 39122334
 
 