Image is illustrative
|
Power Supply Unit TRIO-PS-2G/1AC/48DC/5, 1stk/pck, Phoenix Code:
2903159
Price
Manufacturer
:
Availability:
21 days
|
Weight:
1.12 kg/pc
|
Volume:
0 m3/pc
|
|
|
|
|
Power Supply Unit TRIO-PS-2G/1AC/48DC/5, 1pcs/pck, PhoenixDimensions
Width
|
42 mm
|
Height
|
130 mm
|
Depth
|
160 mm
|
Installation distance right/left
|
0 mm / 0 mm
|
Installation distance top/bottom
|
50 mm / 50 mm
|
Ambient conditions
Degree of protection
|
IP20
|
Inflammability class in acc. with UL 94 (housing / terminal blocks)
|
V0
|
Ambient temperature (operation)
|
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
|
Ambient temperature (start-up type tested)
|
-40 °C
|
Ambient temperature (storage/transport)
|
-40 °C ... 85 °C
|
Max. permissible relative humidity (operation)
|
≤ 95 % (at 25 °C, non-condensing)
|
Climatic class
|
3K3 (in acc. with EN 60721)
|
Degree of pollution
|
2
|
Installation height
|
≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)
|
Input data
Nominal input voltage range
|
100 V AC ... 240 V AC
|
|
110 V DC ... 250 V DC
|
Input voltage range
|
100 V AC ... 240 V AC -15 % ... +10 %
|
|
110 V DC ... 250 V DC ±10 %
|
Dielectric strength maximum
|
≤ 300 V AC 15 s
|
AC frequency range
|
50 Hz ... 60 Hz ±10 %
|
Frequency range (fN)
|
50 Hz ... 60 Hz ±5 Hz
|
Discharge current to PE
|
< 3.5 mA
|
Current consumption
|
2.9 A (100 V AC)
|
|
2.3 A (120 V AC)
|
|
1.2 A (230 V AC)
|
|
1.2 A (240 V AC)
|
Nominal power consumption
|
285.7 VA
|
Mains buffering time
|
typ. 15 ms (120 V AC)
|
|
typ. 15 ms (230 V AC)
|
Input fuse
|
6.3 A (internal (device protection))
|
Recommended breaker for input protection
|
6 A ... 16 A (Characteristics B, C, D, K)
|
Power factor (cos phi)
|
0.91
|
Output data
Nominal output voltage
|
48 V DC ±1 %
|
Setting range of the output voltage (USet)
|
36 V DC ... 55 V DC (> 48 V DC, constant capacity restricted)
|
Nominal output current (IN)
|
5 A
|
Dynamic Boost (IDyn.Boost)
|
7.5 A (5 s)
|
Derating
|
> 60 °C ... 70 °C (2.5%/K)
|
Connection in parallel
|
yes, for redundancy and increased capacity
|
Connection in series
|
yes
|
Feedback voltage resistance
|
≤ 60 V DC
|
Protection against overvoltage at the output (OVP)
|
≤ 60 V DC
|
Control deviation
|
< 1 % (change in load, static 10 % ... 90 %)
|
|
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
|
|
< 0.1 % (change in input voltage ±10 %)
|
Residual ripple
|
< 20 mVPP (with nominal values)
|
Output power
|
240 W
|
Peak switching voltages nominal load
|
< 15 mVPP
|
Maximum power dissipation in no-load condition
|
typ. 4 W (120 V AC)
|
|
typ. 4.1 W (230 V AC)
|
Power loss nominal load max.
|
typ. 24.5 W (120 V AC)
|
|
typ. 20.1 W (230 V AC)
|
Short-circuit current
|
< 7 A DC (Permanent)
|
General
Net weight
|
0.9 kg
|
Efficiency
|
typ. 90.5 % (120 V AC)
|
|
typ. 91 % (230 V AC)
|
MTBF (IEC 61709, SN 29500)
|
> 2000000 h (25 °C)
|
|
> 1200000 h (40 °C)
|
|
> 620000 h (60 °C)
|
Insulation voltage input/output
|
3 kV AC (type test)
|
|
1.5 kV AC (routine test)
|
Degree of protection
|
IP20
|
Protection class
|
I (in closed control cabinet)
|
Inflammability class in acc. with UL 94 (housing / terminal blocks)
|
V0
|
Mounting position
|
horizontal DIN rail NS 35, EN 60715
|
Assembly instructions
|
alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
|
Connection data, input
Connection method
|
Push-in connection
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
4 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
2.5 mm²
|
Conductor cross section AWG min.
|
24
|
Conductor cross section AWG max.
|
12
|
Stripping length
|
10 mm
|
Connection data, output
Connection method
|
Push-in connection
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
4 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
2.5 mm²
|
Conductor cross section AWG min.
|
24
|
Conductor cross section AWG max.
|
12
|
Stripping length
|
8 mm
|
Connection data for signaling
Connection method
|
Push-in connection
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
1.5 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
1.5 mm²
|
Conductor cross section AWG min.
|
24
|
Conductor cross section AWG max.
|
16
|
Stripping length
|
8 mm
|
Standards
EMC requirements for noise immunity
|
EN 61000-6-1
|
|
EN 61000-6-2
|
EMC requirements for noise emission
|
EN 61000-6-3
|
|
EN 61000-6-4
|
Standard - Safety of power supply units up to 1100 V (insulation distances)
|
DIN EN 61558-2-16
|
Standard - Electrical safety
|
IEC 62368-1 (SELV)
|
Standard – Safety extra-low voltage
|
IEC 60950-1 (SELV) and EN 60204-1 (PELV)
|
Standard - Safe isolation
|
DIN VDE 0100-410
|
Standard – Limitation of mains harmonic currents
|
EN 61000-3-2
|
Rail applications
|
EN 50121-4
|
Overvoltage category EN 60950-1
|
II
|
Overvoltage category EN 62477-1
|
III
|
Conformance/approvals
UL approvals
|
UL Listed UL 508
|
|
UL/C-UL Recognized UL 60950-1
|
EMC data
Electromagnetic compatibility
|
Conformance with EMC Directive 2014/30/EU
|
Low Voltage Directive
|
Conformance with Low Voltage Directive 2014/35/EC
|
Conducted noise emission
|
EN 55016
|
|
EN 61000-6-3 (Class B)
|
Noise emission
|
EN 55016
|
|
EN 61000-6-3 (Class B)
|
Electrostatic discharge
|
EN 61000-4-2
|
Contact discharge
|
6 kV (Test Level 4)
|
Discharge in air
|
8 kV (Test Level 4)
|
Electromagnetic HF field
|
EN 61000-4-3
|
Frequency range
|
80 MHz ... 1 GHz
|
Test field strength
|
10 V/m (Test Level 3)
|
Frequency range
|
1 GHz ... 2 GHz
|
Test field strength
|
10 V/m (Test Level 3)
|
Frequency range
|
2 GHz ... 6 GHz
|
Test field strength
|
10 V/m (Test Level 3)
|
Comments
|
Criterion A
|
Fast transients (burst)
|
EN 61000-4-4
|
Input
|
4 kV (Test Level 4 - asymmetrical)
|
Output
|
2 kV (Test Level 3 - asymmetrical)
|
Signal
|
2 kV (Test Level 4 - asymmetrical)
|
Comments
|
Criterion A
|
Surge voltage load (surge)
|
EN 61000-4-5
|
Input
|
2 kV (Test Level 4 - symmetrical)
|
|
4 kV (Test Level 4 - asymmetrical)
|
Output
|
1 kV (Test Level 3 - symmetrical)
|
|
2 kV (Test Level 3 - asymmetrical)
|
Signal
|
1 kV (Test Level 2 - asymmetrical)
|
Comments
|
Criterion A
|
Conducted interference
|
EN 61000-4-6
|
I/O/S
|
asymmetrical
|
Frequency range
|
0.15 MHz ... 80 MHz
|
Voltage
|
10 V (Test Level 3)
|
Comments
|
Criterion A
|
Voltage dips
|
EN 61000-4-11
|
Voltage
|
230 V AC
|
Frequency
|
50 Hz
|
Voltage dip
|
70 %
|
Number of periods
|
25 periods
|
Additional text
|
Test Level 2
|
Comments
|
Criterion A
|
Voltage dip
|
40 %
|
Number of periods
|
10 periods
|
Additional text
|
Test Level 2
|
Comments
|
Criterion A
|
Voltage dip
|
0 %
|
Number of periods
|
1 period
|
Additional text
|
Test Level 2
|
Comments
|
Criterion A
|
Criterion A
|
Normal operating behavior within the specified limits.
|
Criterion B
|
Temporary impairment to operational behavior that is corrected by the device itself.
|
Criterion C
|
Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
|
Environmental Product Compliance
REACh SVHC
|
Lead 7439-92-1
|
China RoHS
|
Environmentally Friendly Use Period = 25;
|
|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
|
ECLASS
ECLASS 10.0.1 |
27040701
|
ECLASS 11.0 |
27040701
|
ECLASS 4.0 |
27040702
|
ECLASS 4.1 |
27040702
|
ECLASS 5.0 |
27049002
|
ECLASS 5.1 |
27049002
|
ECLASS 6.0 |
27049000
|
ECLASS 7.0 |
27049002
|
ECLASS 9.0 |
27040701
|
ETIM
ETIM 4.0 |
EC002540
|
ETIM 6.0 |
EC002540
|
ETIM 7.0 |
EC002540
|
UNSPSC
UNSPSC 13.2 |
39121004
|
UNSPSC 18.0 |
39121004
|
UNSPSC 19.0 |
39121004
|
UNSPSC 20.0 |
39121004
|
UNSPSC 21.0 |
39121004
|
|
File description
|
File type
|
Download link
|
|
|
|
|
|
|
|
|