Image is illustrative
|
Input Module MicroLogix1200, 16-ch., output 24VDC sink/source, LED, TS35, panel mount, Allen-Bradley Code:
1762-IQ16
Price (indicative)
Manufacturer
:
Availability:
21 days
|
Weight:
0.229 kg/pc
|
Volume:
0.0011 m3/pc
|
|
|
|
|
Discrete Input Module MicroLogix 1200, 16-ch., output 24VDC sink/source, LED, TS35/ panel mount, Rockwell Automation
DESCRIPTIONS
MicroLogix™ Digital Input Module, Type: Discrete, Number Of Channels: 16 (Isolated), Input: Off-State Voltage: 5 VDC, Off-State Current: 1.5 MA, On-State Voltage: 10 VDC, On-State Current: 12 MA (Maximum) At 30 VDC, Voltage Rating: 10 - 30/10 - 26.4 VDC, Isolation: Verified By One Of The Following Dielectric Tests: 1200 VAC For 1 SEC Or 1697 VDC For 1 SEC, 75 VDC Working Voltage (IEC Class 2 Reinforced Insulation), Enclosure: IP20, Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ, Mounting: DIN Rail, Panel, Length: 1.59 IN, Width: 3.425 IN, Height: 3.543 IN, Temperature Rating: -4 To 149 DEG F, Environmental Conditions: Relative Humidity: 5 - 95% (Non-Condensing), Vibration: 5 G, Shock - Operating: 30 G, Non-Operating: 50 G (Panel Mount), 40 G (DIN Mount), Response Time: Signal Delay - On Delay: 8 MS, Off Delay: 8 MS, Power Dissipation: Heat Dissipation: 5.4 W At 30 VDC, 4.3 W At 26.4 VDC, Output Type: Current Sinking/Source, Bus Rating: Bus Current Draw: 70 MA At 5 VDC (0.35 W), Impedance: Nominal: 3 KOHM, Surge Transient Immunity: Plus/Minus 1 KV Line-Line(DM) And Plus/Minus 2 KV Line-Earth(CM) On Signal Ports, Indicator: LED, Standard/Approvals: C/US UL listed, UL 508, UL 1604, CSA C22.2, file number 213, CE marked, class I, division 2, hazardous location, groups A, B, C, D, C-tick, GOST_R, KCC certified, marine-ABS, marine-BVS, marine-DNV, marine-GL, marine-KRS, marine-LR, ROSTECHNADZOR
|
|
SPECIFICATIONS
- Item Name: Digital Input Module
- Type: Discrete
- Sub Brand: MicroLogix™
- Number Of Channels: 16 (Isolated)
- Input: Off-State Voltage: 5 VDC, Off-State Current: 1.5 MA, On-State Voltage: 10 VDC, On-State Current: 12 MA (Maximum) At 30 VDC
- Voltage Rating: 10 - 30/10 - 26.4 VDC
- Isolation: Verified By One Of The Following Dielectric Tests: 1200 VAC For 1 SEC Or 1697 VDC For 1 SEC, 75 VDC Working Voltage (IEC Class 2 Reinforced Insulation)
- Enclosure: IP20
- Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ
- Mounting: DIN Rail, Panel
- Length: 1.59 IN
- Width: 3.425 IN
- Height: 3.543 IN
- Temperature Rating: -4 To 149 DEG F
- Environmental Conditions: Relative Humidity: 5 - 95% (Non-Condensing), Vibration: 5 G, Shock - Operating: 30 G, Non-Operating: 50 G (Panel Mount), 40 G (DIN Mount)
- Response Time: Signal Delay - On Delay: 8 MS, Off Delay: 8 MS
- Power Dissipation: Heat Dissipation: 5.4 W At 30 VDC, 4.3 W At 26.4 VDC
- Output Type: Current Sinking/Source
- Indicator: LED
- Surge Transient Immunity: Plus/Minus 1 KV Line-Line(DM) And Plus/Minus 2 KV Line-Earth(CM) On Signal Ports
- Impedance: Nominal: 3 KOHM
- Bus Rating: Bus Current Draw: 70 MA At 5 VDC (0.35 W)
FEATURES
The 1762 MicroLogix expansion I/O modules are compatible with MicroLogix 1100, MicroLogix 1200, and MicroLogix 1400 controllers. Install the expansion I/O modules to the right of the controller, either on a panel with two mounting screws or on a DIN rail. Use digital I/O modules in many combinations, up to the maximum supported by the controller. The current loading capacity of the controller’s built-in power supply may limit the actual number of I/O modules that can be connected to the controller.
Integrated high-performance I/O bus
Software keying to prevent incorrect positioning within the system
Finger-safe terminal blocks for I/O wiring
Label to record I/O terminal designations
Network support includes EtherNet/IP, DeviceNet, and DH-485 (local only)
Standards: C/US UL listed, UL 508, UL 1604, CSA C22.2, file number 213, CE marked, class I, division 2, hazardous location, groups A, B, C, D, C-tick, GOST_R, KCC certified, marine-ABS, marine-BVS, marine-DNV, marine-GL, marine-KRS, marine-LR, ROSTECHNADZOR
|
|
|
|