Differential Pressure Transducer PremasGard SHD 692-I-912, range 0..1bar, liquid, gas media -15..80°C, output 4..20mA 2Draht, screw connection 6mm pipe (G⅛-in. 27NPT int. thread), sv 24VDC, IP65, S+S Regeltechnik
Image is illustrative
Differential Pressure Transducer PremasGard SHD 692-I-912, range 0..1bar, liquid, gas media -15..80°C, output 4..20mA 2Draht, screw connection 6mm pipe (G⅛-in. 27NPT int. thread), sv 24VDC, IP65, S+S Regeltechnik
Code: 1301-4122-0520-000
Price
371,80 €  /pc
Manufacturer :
Availability:
14 days
Weight:
0.7455 kg/pc
 

Differential Pressure Transducer Premasgard SHD 692-I-912, range 0..1bar, liquid ?gas media -15..80°C, output 4..20mA 2wire, screw connection 6mm pipe (G?-in. 27NPT int. thread), sv 24VDC, IP65, S+S Regeltechnik

PREMASGARD® SHD 692-I-912

Item No. 1301-4122-0520-000
EAN 4 251325 617176

The pressure sensor ⁄ differential pressure sensor PREMASGARD® SHD-692 is used to measure pressures in gaseous and liquid media. It converts the measurand into standard signals of 0 -10 V or 4...20mA. Process connection is 2 x G ⅛ " - 27 NPT internal thread. The SHD -692 differential pressure transmitter is used in piping and hydraulic systems, in mechanical and plant engineering as well as in building automation.
Not suitable for ammonia and freon!

Voltage supply 18-33V DC
Response time < 5 ms
Output signal 4...20 mA, 2-wire connection
Measuring range 0... 1 bar
Measuring principle ceramic measuring cell
Media temperature –15...+80 °C
Pressure connection screw pipe connection for 6 mm pipe
(G ⅛ " - 27 NPT internal thread)
Type of pressure differential pressure
Class 0.5 %
Total error < 1.3 %
System pressure max. 25 bar (P1 + P2)
Bursting pressure 1.5 x system pressure
Medium liquid or gaseous
Insulating resistance ≥ 100 MΩ,
at +20 °C (500V DC)
Electrical connection 0.25 - 1.5 mm², DIN EN 175301- 803 - A
Enclosure stainless steel 1.4305
Connecting head angle plug connector DIN EN 175301- 803 - A
Installation installation arbitrary
Medium contacting parts INOX 1.4305, ceramics, sealing material EPDM
Protection class III (according to EN 60 730)
Protection type IP 65 (according to EN 60 529) with receptacle mounted
Standards CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014 ⁄ 30 ⁄ EU
Optional Display module, additional height: approx. 50 mm,
for displaying the pressure
 
 